HomeCalculatorsArc Flash Analysis

Arc Flash Calculator

IEEE 1584:2018 — Electrical Safety & PPE

Phase 3 Calculator

Inputs

Line-to-line or phase-to-neutral

Maximum available short-circuit current

Time until protection operates

Distance from arc source (typically 450 mm)

Enclosed increases incident energy

Results

Incident Energy

1340.33

cal/cm²

Required PPE Category

DANGEROUS

System Voltage0.4 kV
Bolted Fault Current20 kA
Arc Duration0.5 s
Arc Current (Estimated)16.0 kA
Arc Flash Boundary15039 mm
Arc Duration (ms)500 ms

Recommended PPE

DANGEROUS — Do NOT work live. Arc flash energy exceeds safe exposure limits. Implement engineering controls (insulation, guarding, remote operation) or de-energize.

⚠️ High Arc Flash Hazard

Incident energy >25 cal/cm². Avoid live work if possible. Use remote racking or other de-energized methods.

Important: These results are indicative only. Arc flash hazard analysis must be performed by a qualified electrical engineer in accordance with IEEE 1584:2018 and AS/NZS 3000:2018. All calculations must be verified and documented in hazard labels before live work.

Arc Flash Analysis — IEEE 1584:2018

Arc flash is a sudden release of thermal and radiant energy during an electrical fault. This calculator determines the incident energy (cal/cm²) and corresponding PPE (personal protective equipment) category required for safe work on energized electrical equipment. Results must drive safety protocols and labeling on switchboards and distribution equipment.

Electrode Configurations

  • VCB: Vertical configuration, cable insulation in the arc chamber, bare bus.
  • VCBB: Vertical configuration, cable insulation, bare bus outside chamber.
  • HCB: Horizontal configuration, cable in chamber, bare bus.
  • VOA: Vertical configuration, open air (no chamber), insulated and bare bus.
  • HOA: Horizontal configuration, open air, insulated and bare bus.

Key Parameters

  • Bolted Fault Current: Maximum available fault current at the arc location.
  • Arc Duration: Time fault is allowed to persist before protective device operates.
  • Working Distance: Distance of worker >face from arc source (typically arm's reach).
  • Gap Between Conductors: Affects arc voltage and energy release. Smaller gaps increase energy.
  • Enclosure Type: Open air vs enclosed. Enclosures confine and amplify arc energy.

PPE Categories

  • Category 1 (<1.2 cal/cm²): Cotton clothing adequate.
  • Category 2 (1.2–8 cal/cm²): Fire-resistant shirt and pants.
  • Category 3 (8–25 cal/cm²): Aluminized proximity suit + face shield.
  • Category 4 (>25 cal/cm²): Full hazmat suit + SCBA. Avoid work if possible.

Disclaimer: These results are indicative only. Arc flash hazard analysis must be performed by a qualified electrical engineer in accordance with IEEE 1584:2018, AS/NZS 3000:2018, and applicable electrical safety standards. All calculations must be verified and documented in hazard label compliance before workers perform live-work procedures.